π₯ Automatic Gas Extinguisher Control Panel
Model: AW-GEC2169
π‘οΈ Product Overview
The Asenware AW-GEC2169 Automatic Gas Fire Extinguisher Control Panel is designed in compliance with:
-
EN54-2: Fire detection and fire alarm systems β Control & Indicating Equipment
-
EN54-4: Fire detection and fire alarm systems β Power Supply Equipment
-
EN12094-1: Fixed firefighting systems β Electrical automatic control & delay devices
With a modern metal enclosure, glass viewing window, and user-friendly interface, the AW-GEC2169 ensures safe, stable, and reliable firefighting control.
β¨ Product Features
-
πΉ Dual Zone Inputs β Two alarm zone signals, up to 16 detectors per zone
-
πΉ EM Valve Output β Controls electromagnetic valve release
-
πΉ Multiple Panel Outputs β Line fault, alarm, extinguishing signal, 24VDC
-
πΉ Automatic Power Switching β Between AC 220V and backup battery
-
πΉ Three Access Levels β View, operation, and settings
-
πΉ Real-Time Fault Detection β Input, output, power, ground, fuse monitoring
-
πΉ Manual Functions β Disable zones, evacuate, silence alarms, reset
-
πΉ Delay Time Settings β Adjustable release and reset delay (0β60s)
-
πΉ Secure Metal Cabinet β Lockable with glass window
-
πΉ Long-Term Stability β Rigorous factory testing ensures reliability
βοΈ Technical Specifications
Parameter | Specification |
---|---|
AC Input | 220VAC, 50Hz (+10% / β15%) |
DC Output | 24VDC (19β28V) & 5VDC (4.9β5.1V) |
Standby Current | <450mA |
Max Current (Excl. Battery Charge) | 1.4A |
Battery Current | 1.85A (max, current-limited) |
Auxiliary Output | 24VDC, 200mA (max) |
Release Delay Time | 0β60s adjustable (5s steps) |
Battery Type | 2 Γ 12V / 2.3Ah sealed lead-acid |
Low-Voltage Protection | 21V |
Max Detectors per Zone | 16 |
Total CIE Points | 32 (detectors + MCPs) |
Zone Alarm Current | 6mA (min) / 27mA (max) |
Sounder Output | 200mA max |
Routing Outputs (Fire/Fault) | 200mA each |
Communication Protocol | 2-wire RS485 |
EOL Resistor | 6.8KΞ©, 1W |
Recommended Wiring | 220V AC: 16AWG / Panel-Interface: 20AWG / Main Board-Interface: 28AWG |
Fuse Ratings | Power: 3A / General: 0.2A Γ5 / Main: 2A / EM Valve: 1.5A |
Operating Temperature | β5Β°C to +40Β°C |
Humidity | 5β95% RH, non-condensing |
Enclosure | Metal cabinet with glass window |
Terminal Block Rating | 12β18 AWG (0.75β2.5mmΒ²) |
Dimensions | [Not provided β typically depends on cabinet] |
π Applications
π’ Commercial & Industrial Buildings
π Gas Extinguishing Systems
π Educational Institutions
π₯ Hospitals & Healthcare Facilities
π¦ Warehouses & Storage Areas
π¬ Shopping Malls & Public Facilities
Β Available Now at City Fire
β Trusted Quality
β Certified Performance
β Fast Nationwide Delivery